- Displays air Volume flow, Velocity and Temperature in SI, Metric or
Imperial measurements
- No mistakes with colour coded fabric hoods for easy identification
- Free calibration certificate to international standards
- Hoods designed to comply with latest European grille size recommendations
- Easy read, tilting, backlit meter indicates supply or extract flow
- Use in any orientation for wall, ceiling and floor grilles
- ATD value input automatically adjusts for grille correction factors
- Highly accurate - even at low flows - no plate changes required
- Detachable air flow meter for every day use with a choice of vane 35mm
and 100mm diameter sensors
- Pre-assembled hood frames save time on site (unlike metal kits)
- Auto zero, memory, avg/max/min/sum, STP, RS232 for Windows®
- So compact basic kit fits in a 'carry aboard' flight bag
- Perfect for commissioning, facilities managers, health and safety specialists,
test engineers, ventilation contractors and consultants

|

 |
- Choice of six durable, collapsible fabric hood sizes
- Option of three plastic hoods for smaller grilles
- Three fixed opposed handles for ease of handling with finger tip control
button
- Detachable anemometer with 100mm and 35mm vane sensors and articulating
telescopic probe
- Superbly featured air meter with 'real time' and 'recall modes', duct
dimensions and area inputs
- Adjustable display damping for fluctuating flows
- Temperature measurement direct from hood and vane sensor
- No low flow screens to remove and replace Leak tight, tear resistant,
nylon hoods with air cushioned grille seals
- Hoods interchangeable with other leading makes
- Tilting, back-lit flow meter fully protected for on-site knocks
- True ambient readout or STP corrected readings
- Direct download into Windows® software or to portable mini printer
- Calibration certificate, carry case and batteries supplied
- Exceptional value for money.
SPECIFICATIONS
| Volume Flow |
85 to 4078 m3/hr
24 to 1133 L/sec
50 to 2400 CFM |
Velocity Range
(using 100mm vane) |
0.25 to 30 m/sec
50 to 6000 ft/min |
| Temperature Range |
0 to 800C
320 to 1760F |
| ATD Factor Input |
0.1 to 9.0 |
Accuracy
(calibrated better than) |
Supply ± 3% of reading ± 12 m3/hr
Exhaust ± 4% of reading ± 12 m3/hr |
| Display Resolution Volume |
1 m3/hr 1 1/sec 1 CFM |
| Velocity |
0.01 m/sec 1 ft/min |
| Temperature |
0.010C 10F |
| Memory Locations |
99 |
| Digital Output |
RS232 |
| Operating Range |
0 to 500C |
Weight (Instrument and
610x634mm Hood) |
3.8kg (8.3lbs) |
| Compliance |
CE, EMC 89/336/EEC
EN50081-1, EN50082-1 |
|
 |