Model

HY-3000

AF1

AF1(SUB)




Appearance



DIN(mm)
(W)¡¿(H)¡¿(D)

96¡¿96¡¿104

48¡¿96¡¿100

48¡¿96¡¿100

Powervoltage

100-240VAC(50/60Hz)

Power consumption

3VA

Input

R. T. D

Control output

Relay contact: AC 250V 3A(Resistive load), SSR : DC12V (constant voltage pulse load resistance more than 800¥Ø]

Control method

ON/OFF Control of time proportioning

Alarm output


Relay contact : AC 250V 5A

Alarm Setting


Variation setting for SV

External input resistance

Thermo couple : Less than 100¥Ø, R.T.D : Less than 10¥Ø

Setting

Analog setting

by digital switch

Display

Setting value

Indication

Analog

Setting and indication accuracy

Setting temperature ; within ¡¾2.0% in Max,
Display accuracy : within ¡¾2.5% in Max.range

Control sensitivity

less than 0.2% F¡¤S

Proportional cycle

Relay contact : 25¡­30sec SSR : 2¡­4sec

Rest range

¡¾1.5% fo Max. range(Between terminal and earth)

Dielectric strength

AC 2,000V for 1 minute

Vibration

Malfunction

2-55Hz, X, Y, Z each positions for 10 minutes

Durability

10-55Hz, 0.76mm, X, Y, Z each positions for 2 hours

shock

Malfunction

100§¾ 6 positions, Each 3 times

Durability

300§¾ 6 positions, Each 3 times

Life

Mechanical

More than 10 millions times

Electronical

More than 0.3 millions times

Ambient temperature and humidity

0¡­50¡É(32¡­122¢µ)¡¤35¡­85%RH