Model

PX9

PX7

PX2

PX3

Appearance

DIN(mm)
(W)▼(H)▼(D)




96▼96▼100


72▼72▼100



48▼96▼100






96▼48▼100

Function

﹞Fuzzy function                        ﹞Auto-tuning PID      ﹞External contact input     
﹞Reverse/Direct selectable      ﹞Heater break alarm(HBA1, HBA2)

﹞Zone PID                               ﹞Alarm output             ﹞Ramp ㄕ Soak     
﹞Interface(RS 485/422)           
﹞Protection(Front facia IP65)

﹞Group PID      ﹞Multi input-output     ﹞Output limit function     ﹞Set point value 3 steps

Input

Thermo couple: K, J, E, T, R, S, B, L, N, U.WRe 5-26, PL-弗

R.T.D : Pt 100目, KPt 100目

Direct voltage: 1#5V, 1#10V, -10#20mV, 0#100mV(Programmable scale type)

Sampling time

250mS, (When remote option: 500mS)

Cold junction temperature compensation tolerance

▽1.5﹎(15#35﹎), ▽2.0﹎(0#50﹎)

Input impedance

T/C and mV input :1 M目 min, DC V: 1M目

Lead wire tolerable resistance

R.T.D: 150目max. / wire

Input

tolerable voltage

▽10V(T/C, R.T.D, voltage: mV DC)

▽20V (Voltage: V DC)

Noise removal rate

NMRR(Normal mode): 40dB min.

CMRR(Common mode): 120dB min, (50/60Hz ▽1%)

Standard

T/C, R.T.D: KS, IEC, DIN

Scaling

According to setting max. voltage(SH), min. value(SL) of measurement range, scaling is available(-1999#9999)

Standard junction temp. compensation tolerance

▽1.5﹎(15#35﹎), ▽2.0﹎(0#50﹎)

Burn-out

T/C : OFF, Up/Down selectable

R.T.D: OFF, Up/Down selectable(Detection current: 50nA)

Accuracy

▽0.1%(Full scale)