Model
|
MX9-V
|
MX2-V
|
Appearance
DIN(mm)
(W)¡¿(H)¡¿(D)
|
96¡¿96¡¿100
|
48¡¿96¡¿100
|
|
Function
|
Multi input, Heating and cooling PID
control, Break alarm, Ramp funciton, Manual output functink Remoto/Local
input ¡É/¢µselectable, reverse/Direct action selectable
|
|
Power Voltage
|
100-240VAC(50/60Hz)
|
|
Power consumption
|
Less than 15VA
|
|
Input(Multi function)
|
11 kind fo input
|
|
CT INPUT
|
HBA(25.0A or 50.0A)
|
|
Control output
|
Relay contact : AC 250V 5A(Resistive
load),
SSR : 12V DC(constant voltage pulse) [load Resistouce wore than 800¥Ø],
Current:4-20mA DC (load Resistance less than 600¥Ø)
|
|
Control action
|
P.I.D(Auto-tuning funciton) or ON/OFF
|
|
Alarm output
|
Relay Contact Output : AC 250V 0.5A(AL-2),
3A(AL-1) (Resistance lood)
|
|
Heater/
Loop break Alarm
|
LBA.HBA [Relay contact output : AC 250,
3A [Resistance load]
|
|
Setting
|
by the Up/Down key
|
|
Display
|
L.E.D DISPLAY
|
|
Setting and indication accuracy
|
T/C : winthin¡¾3¡É(6¢µ) [Whichever is larger]
R.Input: 0¡199¡É 10¡390¢µ within ¡¾5¡É(10¢µ)
R.T.P : within ¡¾2¡É(3¢µ) (whichever is larger)
|
|
Protection memory
|
Semi-permanent
|
|
Sampling cycle
|
500ms
|
|
Heating cycle
|
1-100sex
|
|
Cooling cycle
|
1-100sec
|
|
Cooling gain
|
Display of 10 times to proportional band
|
|
Cooling deadband
|
-20.0¡20.0¡É(¢µ)
|
|
Input connection range
|
SLU-SLF
|
|
Insulation resistance
|
More than 20§Û Min. (DC500V Mege)
|
|
Dielectric strength
|
AC 2000V 50/60Hz per 1 minute (Between
terminal and earth)
|
|
Vibration
|
Malfunction
|
2-55Hz, X, Y, Z each positions for 10
minutes
|
|
Durability
|
10-55Hz, 0.76mm, X, Y, Z each direction
for 2 hours
|
|
shock
|
Malfunction
|
100§¾ 6 positions, Each 3times
|
|
Durability
|
300§¾ 6 positions, Each 3times
|
|
Life
|
Mechanical
|
More than 10 milions times (Relay type)
|
|
Electronical
|
More than 0.3 milions times (Relay type)
|
|
Ambient temperature and humidity
|
0¡50¡É(32¡122¢µ)¡¤35¡85%RH
|