Model

DX9

DX7

DX2

DX3

DX4




Appearance


DIN(mm)
(W)¡¿(H)¡¿(D)


96¡¿96¡¿100

72¡¿72¡¿100

48¡¿96¡¿100

96¡¿48¡¿100

48¡¿48¡¿100

Function

PID Auto-tuning,  Input correction function,     
Setting control function,  Alarm ALH,  ALL, Decimal point indication

Power voltage

100-240VAC(50/60Hz)

Power consumption

Less than 15VA

Less than 12VA

Input

Thermo couple(K¡¤J¡¤R), R¡¤T¡¤D(DIN/JJS Pt 100¥Ø),mV & mA

Control output

Relay contact output: AC 250V 3A(Resistive load), SSR drive : p12V DC(constant voltage pulse) [load resistance more than 800¥Ø]

Control action

P.I.D(Auto-tuning funciton), ON/OFF, P¡¤PI¡¤PD

Alarm output

Relay Contact Output : AC 250V 0.5A(AL-2, LBA), 3A(Al-a)

Loop break alarm

Relay contact output : AC 250, 3A [Resistance lood]

Setting

by the Up/Down key

Indication

L.E.D DISPLAY(PV: Green, SV: Red)

PV : 14mm
SV : 10.5mm

PV : 11mm
SV : 8mm

PV : 10mm
SV : 8mm

PV : 14mm
SV : 8mm

PV : 8mm
SV : 8mm

Setting and indication accuracy

T/C : winthin¡¾3¡É(6¢µ) [Whichever is larger]

R.Input: 0¡­199¡É 10¡­390¢µ within ¡¾5¡É(10¢µ) R.T.D : within ¡¾5¡É(10¢µ)[Whichever is larger]

Memory protection

Semi-permanent

Dielectric strength

AC 2,000V 50/60Hz per 1 minute (between terminal and earth)

Vibration

Malfunction

2-55Hz, X, Y, Z each positions for 10 minutes

Durability

10-55Hz, 0.76mm, X, Y, Z each positions for 2 hours

shock

Malfunction

100§¾ 6 positions, Each 3 times

Durability

300§¾ 6 positions, Each 3 times

Life

Mechanical

More than 10 millions times (Relay type)

Electronical

More than 0.3 millions times

Ambient temperature and humidity

0¡­50¡É(32¡­122¢µ)¡¤35¡­85%RH