Model

HY-8000S

HY-8200S
(Alam output)

HY-72D

HY-48D




Appearance



DIN(mm)
(W)¡¿(H)¡¿(D)

96¡¿96¡¿125

96¡¿96¡¿125

72¡¿72¡¿110

48¡¿48¡¿110

Power voltage

100-240VAC(50/60Hz)

Power consumption

3VA

Input

Thermo couple(K,J) R.T.D(DIN/JIS Pt l00¥Ø)

Control output

Relay contact: AC 250V 3A(Resistive load),
SSR : DC12V (constant voltage pulse) [load resistance more than 800¥Ø],
Current: 4¡­20mA DC(load resistance less than 600§Û)

Control action

ON/OFF Control of time proportioning

Alarm output


Relay contact:
AC 250 3A


Setting

By B.C.D S/W

External input resistance

Thermo couple : less than 100¥Ø, R.T.D : less than 10¥Ø

Indication range

Setting temperature range

Display

L.E.D DISPLAY

Setting and display accuracy

Less than ¡¾0.5%, Less than ¡¾1.0% of set-value

Control sensitivity

0.2% F¡¤S

Proportional cycle

Relay contact : 25¡­30sec SSR : 2¡­4sec

Rest range

¡¾1.5% fo Max. range

Dielectric strength

AC 2,000V 50/60Hz for 1 minute(Between terminal and earth)

Vibration

Malfunction

2-55Hz, X, Y, Z each positions for 10 minutes

Durability

10-55Hz, 0.76mm, X, Y, Z each positions for 2 hours

shock

Malfunction

100§¾ 6 positions, Each 3 times

Durability

300§¾ 6 positions, Each 3 times

Life

Mechanical

More than 10 millions times (Relay type)

Electronical

More than 0.3 millions times (Relay type)

Ambient temperature and humidity

0¡­50¡É(32¡­122¢µ)¡¤35¡­85%RH