Model
|
HY-8000S
|
HY-8200S
(Alam output)
|
HY-72D
|
HY-48D
|
Appearance
DIN(mm)
(W)¡¿(H)¡¿(D)
|
96¡¿96¡¿125
|
96¡¿96¡¿125
|
72¡¿72¡¿110
|
48¡¿48¡¿110
|
|
Power voltage
|
100-240VAC(50/60Hz)
|
|
Power consumption
|
3VA
|
|
Input
|
Thermo couple(K,J) R.T.D(DIN/JIS Pt l00¥Ø)
|
|
Control output
|
Relay contact: AC 250V 3A(Resistive load),
SSR : DC12V (constant voltage pulse) [load resistance more than 800¥Ø],
Current: 4¡20mA DC(load resistance less than 600§Û)
|
|
Control action
|
ON/OFF Control of time proportioning
|
|
Alarm output
|
|
Relay contact:
AC 250 3A
|
|
|
Setting
|
By B.C.D S/W
|
|
External input resistance
|
Thermo couple : less than 100¥Ø, R.T.D :
less than 10¥Ø
|
|
Indication range
|
Setting temperature range
|
|
Display
|
L.E.D DISPLAY
|
|
Setting and display accuracy
|
Less than ¡¾0.5%, Less than ¡¾1.0% of set-value
|
|
Control sensitivity
|
0.2% F¡¤S
|
|
Proportional cycle
|
Relay contact : 25¡30sec SSR : 2¡4sec
|
|
Rest range
|
¡¾1.5% fo Max. range
|
|
Dielectric strength
|
AC 2,000V 50/60Hz for 1 minute(Between
terminal and earth)
|
|
Vibration
|
Malfunction
|
2-55Hz, X, Y, Z each positions for 10 minutes
|
|
Durability
|
10-55Hz, 0.76mm, X, Y, Z each positions
for 2 hours
|
|
shock
|
Malfunction
|
100§¾ 6 positions, Each 3 times
|
|
Durability
|
300§¾ 6 positions, Each 3 times
|
|
Life
|
Mechanical
|
More than 10 millions times (Relay type)
|
|
Electronical
|
More than 0.3 millions times (Relay type)
|
|
Ambient temperature and humidity
|
0¡50¡É(32¡122¢µ)¡¤35¡85%RH
|